Replacement of the electromagnetic exciter of the turbine generator TV-60-2 and ARZ type POA with a single-group two-channel thyristor self-excitation system implementing redundancy schemes (1+1) with microprocessor-based ARV and AWP for monitoring turbine generators TG-5, TG-6, TG-7
CLIENT
Ltd. “Euro-Rekonstruktsia”
YEARS OF IMPLEMENTATION
2017—2021
TYPE OF WORKS
Design, installation works, equipment supply, software development, complex tests and commissioning works
Equipment used, specifics of works provided
- The works starting with dismantling the old system finishing with grid connection to the Ukrainian power system with 60 MW output for TG-5 took 41 days, including dismantling, installation, connection of power and control circuits, as well as comprehensive testing and commissioning.
- The excitation system SSTE-800-250-2.5-UHL4 (SPE “PREOFRESHCHATELNAYA TECHNIKA”) is a Ukrainian development, the field damping system is developed under a Ukrainian patent.
- The power transformer TSZP-630/10-UZ (PE “ELTIZ”) 630 kVA, 10.5 kV/0.475 kV, U/D-11 and the microprocessor-based relay protection device RZL-01 (LLC “SPE “RELSIS”) are also developed by Ukrainian companies.
- The premises with the excitation system equipment were air-conditioned by MIDEA MFM-48 column air conditioners.
- As part of the comprehensive testing and commissioning, thermal imaging surveys of the power thyristor sections and process oscillography were performed using the ADC-BS-8V-9C digital recorder of electrical parameters.
- Digital models of the turbine generator were used to develop the field damping system and to adjust the current, voltage, and reactive power controllers.
Design
Installation works
Equipment supply
Software development
Complex tests
Commissioning works
Similar projects
Complete preventive inspection, restorative maintenance (K(V)), and testing of the ССТП-3500-465-2,5...
Construction, installation, and commissioning works for the reconstruction of the first power unit w...
Development of an independent thyristor excitation system SNVTG-600-200-1.6-UHL4 for the project ...
Modernization of st. #1 turbogenerator. Replacement of the electromagnetic exciter with a thyristor ...
Reconstruction of power unit No. 7 with a capacity of 800 MW. Reconstruction of the control system t...
Reconstruction of the excitation system of a 25 MW turbine generator (replacement of the VT-120-3000...
Replacement of the existing single-channel thyristor self-excitation system type STS-300-2000-2,5-UH...
Supply of thyristor self-excitation systems for hydrogenerators of SSGG-1250-460-2UHL4 type
Technical re-equipment of the st. #. 1 excitation system G-1 TVV-320 (thermal power plant (TPP)
Got questions?
Want to know more about our products or services? Please, fill in the form, and our Customer Relations Manager will contact you as soon as possible!
Message us 