Catalog

We manufacture advanced high-quality products which comply with the Ukrainian and international standards of quality.

PKKZ-10 Series 10 kV Sets of outdoor distribution substations

Description

PKKZ-12-series sets of outdoor distribution substations are designed for connecting various mobile consumers to high-voltage power lines: excavators, drilling units, dredgers, compressors, capacitor banks, and for installation in trunk and branch networks.

PKKZ-12-series  sets of outdoor distribution substations are separate compartments equipped with devices according to their functional purpose.

PKKZ-12-series compartments are used to power and protect the electrical equipment of large quarry energy consumers in distribution networks.

Design:

PKKZ-12-series compartment is a welded metal structure with integrated high-voltage equipment and connections, as well as measuring, signaling, protection, and control devices, made of high-quality steel sheets using precision machinery.

PKKZ-12 compartment is divided into three main sections:

– circuit breaker section;

– busbar section;

– control section.

PKKZ-12-series compartments of integrated outdoor distribution units include a system of mechanical and electromechanical interlocks that complies with all the safety requirements of state standards and other regulatory documents.

 

Designations of PKKZ-12-series compartments:

 

 

Key technical specifications of PKKZ-12-series sets of outdoor distribution substations:

 

Technical parameters

Parameter value

Rated voltage, kV

6; 10

Maximum operating voltage, kV

7,2; 12

Rated busbar current, A

630, 1250, 1600

Rated circuit breaker disconnection current, kA

16; 20; 25;31,5

Thermal withstand current (short-time current), kA*

16; 20; 25; 31,5

Duration of thermal withstand current, sec

3

Rated electromagnetic withstand current of main circuits, kA

51, 63; 81

Rated power of built-in transformers, kVA

25, 40

Rated voltage of auxiliary circuits, V:

AC

110, 220

Insulation level according to GOST 1516.1

Level B

Type of insulation

air

Insulation for current-conducting parts

with uninsulated busbars

Maintenance conditions

with double-sided maintenance

Type of high-voltage connections

cable/aerial

Degree of protection according to GOST 14254

IP34

Climate version according to GOST-15150-69

У1

 