KSO-series prefabricated chambers of single-sided service are designed for equipping distribution units with a voltage of 6 or 10 kV AC and an industrial frequency of 50 Hz, in systems with either an isolated or arc-suppression reactor grounded neutral. The chambers are intended for indoor installation. KSO units are manufactured with stationary mounted switching devices. Our company can produce virtually any construction from the available KSO chambers (KSO of the 2nd series and KSO of the 3rd series). Apart from that, we can manufacture non-standard compartments according to the customer’s technical specifications.
Design:
The chambers are a metal structure assembled from bent profiles connected with rivet-bolt joints.
The frames of the chambers are manufactured in two models:
- Using zinc (Zn) or aluminum-zinc (Al-Zn) coated steel
- Using uncoated structural steel
All components of the frame are coated with powder paint that is resistant to mechanical damage, which ensures high corrosion resistance and extends the service life.
Designations of KSO-series prefabricated chambers:

Key technical specifications of KSO-series prefabricated chambers:
| Technical parameters |
Parameter value |
| Rated voltage, kV |
6; 10 |
| Maximum operating voltage, kV |
7,2; 12 |
| Rated busbar current, A |
400-1600 |
| Nominal current of the main circuits of the chambers with load switch, A |
400; 630 |
| Nominal current of the main circuits of the chambers with vacuum switch, A |
400-1600 |
| Rated circuit breaker disconnection current, kA |
16; 20; 25;31,5 |
| Thermal withstand current (short-time current), kA |
16; 20; 25; 31,5 |
| Duration of thermal withstand current, sec |
3 |
| Rated electromagnetic withstand current of main circuits, kA |
51 |
| Rated voltage of auxiliary circuits, V:
DC AC |
24, 48, 110, 220 24, 48, 100*, 127*, 220 |
| Insulation level according to GOST 1516.1 |
normal |
| Type of insulation |
combined |
| Insulation for current-conducting parts |
with uninsulated busbars; with insulated busbars; with partly insulated busbars |
| Maintenance conditions |
with single-sided maintenance |
| Type of high-voltage connections |
cable/busbar |
| Degree of protection according to GOST 14254 |
IP20 – for external casings of the facade and side panels; IP00 – for the other part of the chambers. |
**Voltages for which the switch-on and switch-off circuits of the circuit breaker drive can be additionally implemented.