K-47 Series 10 kV Sets of distribution substations
Description
K-47 Series sets of distribution substations (KRPZ) are designed for operation in three-phase AC electrical installations with a frequency of 50 Hz and a voltage class of 6–10 kV, in networks with an isolated or arc-suppression reactor-grounded neutral.
K-47 Series KRPZ is used for equipping open-type transformer substations, power generation facilities, and electricity distribution sites.
There are three options for installation:
– on a prepared concrete pad;
– on sleepers;
– on a movable platform (skids).
The advantage of K-47 Series KRPZ over other KRPZ models is its ability to connect directly with K-13, K-37, and K-59 series KRP without the need for transition cabinets, ensuring convenient and fast on-site installation.
Design:
K-47 Series KRPZ is a rigid welded metal structure assembled on a solid base.
To ensure enhanced localization capability, K-47 Series KRPZ is divided into compartments by metal partitions:
- corridor
- busbar compartment
- withdrawable element compartment
- relay compartment
- input/output compartment
The cabinets of K-47 Series KRPZ are equipped with mechanical and electromagnetic interlocks, ensuring safe maintenance by operating personnel.
Key technical specifications of K-47-series sets of outdoor distribution substations:
| Technical parameters |
Parameter value |
| Rated voltage, kV |
6; 10 |
| Maximum operating voltage, kV |
7,2; 12 |
| Rated busbar current, A |
630, 1250, 1600, 2000, 2500, 3150 |
|
Rated circuit breaker disconnection current, kA |
16; 20; 25;31,5 |
| Thermal withstand current (short-time current), kA* |
16; 20; 25; 31,5 |
| Duration of thermal withstand current, sec |
3 |
| Rated electromagnetic withstand current of main circuits, kA |
51, 63; 81 |
| Rated power of built-in transformers, kVA |
25, 40 |
| Rated voltage of auxiliary circuits, V:
DC AC |
24, 48, 110, 220 24, 48, 100*, 127*, 220 |
| Insulation level according to GOST 1516.1 |
normal |
| Type of insulation |
air |
| Insulation for current-conducting parts |
with uninsulated busbars |
| Maintenance conditions |
with double-sided maintenance |
| Type of high-voltage connections |
cable/busbar/aerial |
| Degree of protection according to GOST 14254 |
IP34 |
| Climate version according to GOST-15150-69 |
У1 |